Loading...
Call Us : +974 7776 7420 | 5035 6777
Office Timings: Saturday to Thursday 8:30 to 18:00 - Friday closed

Foam Conductivity Test

Proportioning Testing of Fire Fighting Foam

Verifying that a firefighting foam system accurately proportions foam and water is critical to the system’s effectiveness in the event of a fire. If the premix solution is mixed too lean—not enough foam concentrate and too much water—it may not be able to extinguish the fire. If the premix solution is mixed too rich—too much foam concentrate and not enough water— there is a risk running out of foam before the fire is fully extinguished.

NFPA 25 – Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, 2014 Edition, recommends that foam systems be flowed annually and that the foam solution be tested to verify the concentration.

Furthermore, NFPA 11 – Standard for Low-, Medium-, and High-Expansion Foam, 2010 Edition recommends the following in Section 11.6.4 – “Foam concentration shall have one of the following proportions:

In order to calculate the concentration of the foam solution using either refractive index or conductivity, foam and water are mixed at known concentrations and the refractive index or conductivity of the known solutions are compared to the unknown system solution. In order to ensure accuracy, the following items should be considered:

Often times, the proportioning verification is completed in the field. The advantage of field verification is the system can be immediately adjusted should it be out of specification. However, the advantage of running the verification testing in a laboratory, is the values will be more accurate. This is because the mixing and testing is more accurate and the variables affecting the result can be controlled. Should you determine laboratory testing is required, a representative sample of the concentrate and water must be sent to the laboratory along with a sample of the solution generated from the system.

WhatsApp